PERANCANGAN DATA LOGGER BERBASIS WEB MENGGUNAKAN RASPBERRY PI DI PERUMDAM TIRTA PERWIRA PURBALINGGA

Autor(s): Waridatul Ninda, Dody Wahjudi, Eko Sudaryanto
DOI: 10.53810/jt.v25i1.529

Abstract

Abstrak
Perkembangan industri saat ini mengalami kemajuan pesat. Salah satu contohnya yaitu sistem monitoring jarak
jauh melalui data logger. Studi ini berfokus pada pengembangan "Perancangan Data Logger Berbasis Web
Menggunakan Raspberry Pi" di Perumdam Tirta Perwira. Tujuan utamanya adalah merancang sistem yang
memantau debit air secara real-time melalui alamat web server. Rancangan ini memungkinkan penggunaan
Raspberry Pi 3 Model B+ dan monitoring debit air melalui Ultrasonic Flow Meter. Perancangan dimulai dengan
merancang hardware yang melibatkan penggunaan sensor ultrasonik yang terintegrasi dengan Ultrasonic Flow
Meter (UFM). Data dari UFM akan dikirimkan ke Raspberry Pi kemudian ke platform Blynk melalui MAX3232
to TTL serial converter. Pada pengujian perangkat keras, dilakukan pengujian tegangan. Hasilnya menunjukkan
error pengukuran tegangan input Raspberry Pi sebesar 4,5% dan output sebesar 2,4%, dengan akurasi masingmasing 95,5% dan 97,6%. Pengujian MAX3232 to TTL Serial Converter menghasilkan error pengukuran sebesar
2,22%, dengan akurasi sekitar 97,78%. Pengujian respon alat berhasil menunjukkan bahwa data dapat termonitor
pada laptop dan sesuai dengan data yang keluar dari Ultrasonic Flow Meter (UFM). Hasil pengujian
mengindikasikan variasi aliran air selama pengujian. Rancangan ini diharapkan dapat membawa manfaat
signifikan dalam pemantauan sumber daya air dan teknologi berbasis Raspberry Pi.
Kata Kunci : Data Logger, Raspberry Pi, Ultrasonic Flow Meter.
Abstract
Industrial development is currently experiencing rapid progress. One example is a remote monitoring system via
data logger. This study focuses on the development of "Designing a Web-Based Data Logger Using Raspberry
Pi" at Perumdam Tirta Perwira. The main goal is to design a system that monitors water discharge in real-time
via a web server address. This design allows the use of a Raspberry Pi 3 Model B+ and monitoring water flow
via an Ultrasonic Flow Meter. The design begins with designing hardware which involves the use of an ultrasonic
sensor integrated with an Ultrasonic Flow Meter (UFM). Data from UFM will be sent to the Raspberry Pi then
to the Blynk platform via the MAX3232 to TTL serial converter. In hardware testing, stress testing is carried out.
The results show that the Raspberry Pi input voltage measurement error is 4.5% and the output is 2.4%, with an
accuracy of 95.5% and 97.6% respectively. Testing MAX3232 to TTL. The Serial Converter produces a
measurement error of 2.22%, with an accuracy of around 97.78%. Testing the response of the tool successfully
showed that the data could be monitored on the laptop and matched the data coming out of the Ultrasonic Flow
Meter (UFM). The test results indicate variations in water flow during the test. This design is expected to bring
significant benefits in monitoring water resources and Raspberry Pi-enabled technology.
Keywords : Data Logger, Raspberry Pi, Ultrasonic Flow Meter.

Full Text: